♦ ATEX ELECTRIC BOXES (MP 17 ATEX 0109X)
♦ ATEX ELECTRIC BOXES (MP 17 ATEX 0112X)
♦ ATEX ELECTRIC BOXES (MP 17 ATEX 0114X)
♦ ATEX ELECTRIC BOXES (MP 20 ATEX 0268X)
- Airmeex Electric Boxes are manufactured to meet the requirements of the standards of the relevant protection classes specified below for use in underground and aboveground applications within the scope of 2014/34/EU ATEX Regulation.
- As a flameproof enclosure, electrical cabinets undertake the task of protecting dangerous electrical components or installations for vehicles or engines installed in hazardous areas.
- Designed for connection of intrinsically safe and non-intrinsically safe circuits.
- Electric cabinets consist of two parts: aluminum casting, stainless steel or bronze casting depending on the purpose of use, body and cover.
- Bronze for underground is produced from aluminum with a magnesium ratio not exceeding 6% for above ground.
- Cable entries are from 1/4” to 1”NPT.
- Maximum voltage: 90V
- Maximum dissipated power: 100W
ATEX ELECTRIC BOXES MP 17 ATEX 0109X |
CERTIFICATE NUMBER : ↓ | PROTECTION CLASS : ↓ |
MP 17 ATEX 0109X | Group I : |
I M2 Ex db I Mb | |
WORKING ENVIRONMENT TEMPERATURE : ↓ | Group II : |
-40 ºC ~ +85ºC | II 2G Ex db IIB T6 Gb |
II 2D Ex tb IIIC T85ºC IP6X Db | |
LABEL DESCRIPTION : ↓ | |
AMK y z | REFERENCE STANDARD : ↓ |
EN 60079-0, EN 60079-1, EN 60079-31 |
ATEX ELECTRIC BOXES MP 17 ATEX 0112X |
CERTIFICATE NUMBER : ↓ | PROTECTION CLASS : ↓ |
MP 17 ATEX 0112X | Group I : |
I M2 Ex db I Mb | |
WORKING ENVIRONMENT TEMPERATURE : ↓ | Group II : |
-40 ºC ~ +65ºC | II 2G Ex db IIB T6 Gb |
II 2D Ex tb IIIC T85ºC IP6X Db | |
LABEL DESCRIPTION : ↓ | |
AMK y z | REFERENCE STANDARD : ↓ |
EN 60079-0, EN 60079-1, EN 60079-31 |
ATEX ELECTRIC BOXES MP 17 ATEX 0114X |
CERTIFICATE NUMBER : ↓ | PROTECTION CLASS : ↓ |
MP 17 ATEX 0114X | Group I : |
I M2 Ex db I Mb | |
WORKING ENVIRONMENT TEMPERATURE : ↓ | Group II : |
-40 ºC ~ +65ºC | II 2G Ex db IIB T6 Gb |
II 2D Ex tb IIIC T85ºC IP6X Db | |
LABEL DESCRIPTION : ↓ | |
AMK y z | REFERENCE STANDARD : ↓ |
EN 60079-0, EN 60079-1, EN 60079-31 |
ATEX ELECTRIC BOXES MP 20 ATEX 0268X |
CERTIFICATE NUMBER : ↓ | PROTECTION CLASS : ↓ |
MP 20 ATEX 0268X | Group I : |
I M2 Ex db I Mb | |
REFERENCE STANDARD : ↓ | Working Environment Temperature : -40ºC ~ +60ºC |
EN 60079-0, EN 60079-1, EN 60079-31 | Group II : |
II 2G Ex db IIB+H2 T6 Gb | |
LABEL DESCRIPTION : ↓ | II 2D Ex tb IIIC T85ºC IP65 Db |
AMK y z | Working Environment Temperature : -40ºC ~ +60ºC |
Group I : | |
I M2 Ex db [ib Mb] I Mb | |
Working Environment Temperature : -20ºC ~ +60ºC | |
Group II : | |
II 2G Ex db [ib Gb] IIB+H2 T6 Gb | |
II 2D Ex tb [ib Db] IIIC T85ºC IP65 Db | |
Working Environment Temperature : -20ºC ~ +60ºC |