Atex Electric Boxes

Technical information

♦ ATEX ELECTRIC BOXES (MP 17 ATEX 0109X)

♦ ATEX ELECTRIC BOXES (MP 17 ATEX 0112X)

♦ ATEX ELECTRIC BOXES (MP 17 ATEX 0114X)

♦ ATEX ELECTRIC BOXES (MP 20 ATEX 0268X) 

  • Airmeex Electric Boxes are manufactured to meet the requirements of the standards of the relevant protection classes specified below for use in underground and aboveground applications within the scope of 2014/34/EU ATEX Regulation.
  • As a flameproof enclosure, electrical cabinets undertake the task of protecting dangerous electrical components or installations for vehicles or engines installed in hazardous areas.
  • Designed for connection of intrinsically safe and non-intrinsically safe circuits.
  • Electric cabinets consist of two parts: aluminum casting, stainless steel or bronze casting depending on the purpose of use, body and cover.
  • Bronze for underground is produced from aluminum with a magnesium ratio not exceeding 6% for above ground.
  • Cable entries are from 1/4” to 1”NPT.
  • Maximum voltage: 90V 
  • Maximum dissipated power: 100W 
ATEX ELECTRIC BOXES MP 17 ATEX 0109X
CERTIFICATE NUMBER :  PROTECTION CLASS : ↓
MP 17 ATEX 0109X Group I :
  I M2 Ex db I Mb
WORKING ENVIRONMENT TEMPERATURE : ↓ Group II :
-40 ºC ~ +85ºC II 2G Ex db IIB T6 Gb
  II 2D Ex tb IIIC T85ºC IP6X Db
LABEL DESCRIPTION : ↓  
AMK  y   z REFERENCE STANDARD : ↓
  EN 60079-0, EN 60079-1, EN 60079-31

 

ATEX ELECTRIC BOXES MP 17 ATEX 0112X
CERTIFICATE NUMBER :  PROTECTION CLASS : ↓
MP 17 ATEX 0112X Group I :
  I M2 Ex db I Mb
WORKING ENVIRONMENT TEMPERATURE : ↓ Group II :
 -40 ºC ~ +65ºC II 2G Ex db IIB T6 Gb
  II 2D Ex tb IIIC T85ºC IP6X Db
LABEL DESCRIPTION : ↓  
 AMK  y   z REFERENCE STANDARD : ↓
  EN 60079-0, EN 60079-1, EN 60079-31

 

ATEX ELECTRIC BOXES MP 17 ATEX 0114X
CERTIFICATE NUMBER :  PROTECTION CLASS : ↓
MP 17 ATEX 0114X Group I :
  I M2 Ex db I Mb
WORKING ENVIRONMENT TEMPERATURE : ↓ Group II :
 -40 ºC ~ +65ºC II 2G Ex db IIB T6 Gb
  II 2D Ex tb IIIC T85ºC IP6X Db
LABEL DESCRIPTION : ↓  
AMK  y   z REFERENCE STANDARD : ↓
  EN 60079-0, EN 60079-1, EN 60079-31

 

ATEX ELECTRIC BOXES MP 20 ATEX 0268X
CERTIFICATE NUMBER :  PROTECTION CLASS : ↓
MP 20 ATEX 0268X Group I :
  I M2 Ex db I Mb
REFERENCE STANDARD : ↓ Working Environment Temperature : -40ºC ~ +60ºC 
EN 60079-0, EN 60079-1, EN 60079-31  Group II :
  II 2G Ex db IIB+H2 T6 Gb
LABEL DESCRIPTION : ↓ II 2D Ex tb IIIC T85ºC IP65 Db
AMK  y  z  Working Environment Temperature : -40ºC ~ +60ºC 
  Group I :
  I M2 Ex db [ib Mb] I Mb
  Working Environment Temperature : -20ºC ~ +60ºC 
  Group II :
  II 2G Ex db [ib Gb] IIB+H2 T6 Gb 
  II 2D Ex tb [ib Db] IIIC T85ºC IP65 Db
  Working Environment Temperature : -20ºC ~ +60ºC